Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please provide last approved site plan.
2. Please provide special inspection certifications as outline on sheet S0.1 for review and approval.
3. Please provide structural calculations for all roof top mounted HVAC equipment.
4. Please remove the duplicate sheet T1.1 that is not revised.
SHEET T1.1
5. Please rework your occupancy load: business load is 1/100 not 1/30, exercise is 1/50 not 1/300. Please break down your occupancy uses to as designed use areas:
a. Need to break off area behind climbing wall.
b. Please clarify mezzanine "Party/Training" use, use worst condition for load calculation.
c. Please be more specific about use of Private room, use worst occupancy use load.
d. Please show all loads for different use areas including a ground and mezzanine level breakdown.
e. Once a new occupancy load total has been confirmed, please recalculate required exits and toilet fixture counts.
6. Room 109, the Clean Room, is referred to on the MEP drawings as a loading and storage room. Please reconcile.
a. As per the 2006 IBC, Section 1014.2, one cannot exit through a storage room. See exception 2.
7. Insure that all owner installed millwork is accessible code compliant.
SHEET A1.2
8. For wall type W5, detail 7/A5.1 with wood framing is probably more appropriate than reference detail 8/A5.1.
SHEET A1.3
9. Show location of toilet room signage on detail 1.
10. At detail 3, ADA INSTALLATION STANDARDS: All these standards need to be applied directly to details 1, 2 and 4 and referenced to the 2006 IBC, Chapter 11 and ICC/ANSI 117.1, 2003 Edition for accessible code requirements.
SHEET A5.1
11. Please finish dimensioning and detailing the stair details: length dimension, riser and tread quantity and height and depth.
12. At details 7 and 8: Please show stud framing.
END OF REVIEW
07/12/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Specify the floor drain to be used for the field-fabricated mop sink/cleaning station, P10. Provide installation details to show how the floor of the mop sink/cleaning station will be rendered impervious to water and prevent water leakage past the floor drain. Reference: Sections303.4, 402.2, and 417.5.2, IPC 2006.
07/12/2011 ROBERT SHERRY WATER REVIEW Approved
07/12/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

If 109 is a storage room as stated on Sheet A1.2 the second exit cannot go through it. See IFC Section 1014.2.

The second exit must have panic hardware and cannot have dead bolts on doors 109 B and C. See IFC Section 1008.1.9.

The exits tmust also have exit signs and lights. See IFC Section 1011.
07/15/2011 GERRY KOZIOL WWM REVIEW Denied NEED URINAL CLAIRIFICATION (WATER SCHEMATIC P2.1 SHOWS CONNECTED TO WATER. PLUMBING SCHEDULE P3.1 SHOWS WATERLESS)
NEED 5TH FLOOR CREDIT EVALUATION FOR USER FEE & FIXTURES DEMOLISHED
07/20/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
07/25/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved