Permit Number: T11CM02064
Parcel: 105110630

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02064
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2011 GERRY KOZIOL WWM REVIEW Approved
07/01/2011 RONALD BROWN ADA REVIEW Passed
07/01/2011 MARTIN BROWN FIRE REVIEW Approved
07/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide structural calculations for the wall mounted water heater including evaluation of the partition structural capabilities.
2. Your electrical drawings have lettering smaller than COT minimum size of 3/32" upper and lower case.
END OF REVIEW
07/18/2011 ROBERT SHERRY WATER REVIEW Approved
07/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The City of Tucson allows either the 2006 International Plumbing Code or the 2006 Uniform Plumbing Code to be used for the minimum basis of design but not both codes. The architectural title sheet lists both codes as applicable and the plumbing drawings appear to have been designed primarily per the 2006 UPC with portions based on the 2006 IPC. The plumbing drawings have been reviewed to the 2006 UPC as amended by the City of Tucson.
2. Provide a vacuum relief valve for the water heater. Reference: Section 608.7, UPC 2006.
3. Provide cleanouts that are the same nominal size as the pipes that they serve. Reference: Section 707.11, UPC 2006.
07/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Confirm the sequence of operation for the restroom exhaust fan results in all of the air supplied to the restrooms being exhausted (i.e. the exhaust fan is to run whenever air is being supplied to the restroom). The mechanical plans call for an independent switch for the fan but the electrical plans call for the exhaust fan to be interconnected with the room lights. Reference: Section 403.2.1 (4), IMC 2006.
07/20/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02064
4230 N Oracle Rd #120
TI Retail

1. All lettering and numbering required to be 3/32" min, per City of Tucson Submittal Requirements,see electrical sheets.
2. The sequence of operation of air supplied and exhausted in the restrooms to be interlocked. See Mechanical Plans Examiner comments.

Ray T Majuta
Elect Pln Ck,PDSD,
City of Tucson
7/23/11
Ray.majuta@tucsonaz.gov
07/26/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
07/28/2011 SUE REEVES REJECT SHELF Completed