Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02064
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/01/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 07/01/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/11/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations for the wall mounted water heater including evaluation of the partition structural capabilities. 2. Your electrical drawings have lettering smaller than COT minimum size of 3/32" upper and lower case. END OF REVIEW |
| 07/18/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The City of Tucson allows either the 2006 International Plumbing Code or the 2006 Uniform Plumbing Code to be used for the minimum basis of design but not both codes. The architectural title sheet lists both codes as applicable and the plumbing drawings appear to have been designed primarily per the 2006 UPC with portions based on the 2006 IPC. The plumbing drawings have been reviewed to the 2006 UPC as amended by the City of Tucson. 2. Provide a vacuum relief valve for the water heater. Reference: Section 608.7, UPC 2006. 3. Provide cleanouts that are the same nominal size as the pipes that they serve. Reference: Section 707.11, UPC 2006. |
| 07/18/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Confirm the sequence of operation for the restroom exhaust fan results in all of the air supplied to the restrooms being exhausted (i.e. the exhaust fan is to run whenever air is being supplied to the restroom). The mechanical plans call for an independent switch for the fan but the electrical plans call for the exhaust fan to be interconnected with the room lights. Reference: Section 403.2.1 (4), IMC 2006. |
| 07/20/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02064 4230 N Oracle Rd #120 TI Retail 1. All lettering and numbering required to be 3/32" min, per City of Tucson Submittal Requirements,see electrical sheets. 2. The sequence of operation of air supplied and exhausted in the restrooms to be interlocked. See Mechanical Plans Examiner comments. Ray T Majuta Elect Pln Ck,PDSD, City of Tucson 7/23/11 Ray.majuta@tucsonaz.gov |
| 07/26/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/28/2011 | SUE REEVES | REJECT SHELF | Completed |