Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02013
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/28/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/28/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 06/28/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; FLOOR PLAN: REVISE THE SCALE ON THIS PLAN. 2. GENERAL: PROVIDE ENLARGED PLANS OF TOILET 1 AND TOILET 2. IT DOES NOT APPEAR THE PLANS MATCH THE INTERIOR ELEVATIONS 2 AND 3 ON SHEET A3. PROVIDE CRITICAL DIMENSIONS ON THE PLANS. |
| 06/28/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006. |
| 06/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide sheet P.1 and coordinate the drawing index with the drawing set. Provide a waste and vent diagram for the new work. |
| 06/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | . |
| 06/29/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/29/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/08/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/08/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |