Permit Number: T11CM02013
Parcel: 13316030G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02013
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 STEVE SHIELDS ZONING REVIEW Approved
06/28/2011 LOREN MAKUS ENGINEERING REVIEW Approved
06/28/2011 ERIC NEWCOMB ADA REVIEW Passed
06/28/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; FLOOR PLAN: REVISE THE SCALE ON THIS PLAN.
2. GENERAL: PROVIDE ENLARGED PLANS OF TOILET 1 AND TOILET 2. IT DOES NOT APPEAR THE PLANS MATCH THE INTERIOR ELEVATIONS 2 AND 3 ON SHEET A3. PROVIDE CRITICAL DIMENSIONS ON THE PLANS.
06/28/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
06/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide sheet P.1 and coordinate the drawing index with the drawing set.
Provide a waste and vent diagram for the new work.
06/29/2011 ROBERT SHERRY WATER REVIEW Approved .
06/29/2011 DAVE MANN FIRE REVIEW Approved
06/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/08/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2011 DELMA ROBEY OUT TO CUSTOMER Completed