Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02012
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/15/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/15/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | CLARIFY WALLL TYPES PP A2.0 FULLY DIMENSION RESTROOM ELEVATIONS PP A5.O (GRAB BARS, LAVS, MIRRORS, WC'S, ETC) |
07/15/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11cm02012 1610 W Valencia #100 The electrical plans have been denied for the following: 1. The new service being created for this space cannot be spliced into the existing pull box, the existing service entrance conductors are already designated for a run to the existing service, if there was an available CT enclousure of sufficient capacity, the tie could be accomplished at this point. This Jurisdiction does not allow splices for different meters in a pull box. The utility company would also have issues with this, if there is no available CT enclosure to tie into, the new service would have to be tied into the Utility Transformer. The services are required to be grouped. Ray Majuta, Elect Pln Ck, City of Tucson PDSD, Ray.majuta@tucsonaz.gov |
08/01/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |