Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02012
Parcel: 13727652A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02012
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/15/2011 MARTIN BROWN FIRE REVIEW Approved
07/15/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied CLARIFY WALLL TYPES PP A2.0

FULLY DIMENSION RESTROOM ELEVATIONS PP A5.O (GRAB BARS, LAVS, MIRRORS, WC'S, ETC)
07/15/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm02012
1610 W Valencia #100

The electrical plans have been denied for the following:

1. The new service being created for this space cannot be spliced into the existing pull box, the existing service entrance conductors are already designated for a run to the existing service, if there was an available CT enclousure of sufficient capacity, the tie could be accomplished at this point. This Jurisdiction does not allow splices for different meters in a pull box. The utility company would also have issues with this, if there is no available CT enclosure to tie into, the new service would have to be tied into the Utility Transformer.
The services are required to be grouped.

Ray Majuta,
Elect Pln Ck, City of Tucson
PDSD,
Ray.majuta@tucsonaz.gov
08/01/2011 GERRY KOZIOL WWM REVIEW Approved