Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02012
Parcel: 13727652A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02012
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 STEVE SHIELDS ZONING REVIEW Approved
06/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/28/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PROVIDE IECC LIGHTING CODE COMPLIANCE CERTIFICATE.

PLEASE INDICATE LOCATION OF EXISTING SERVICE

PP 5.0 PROVIDE CURRENT CAPACITY OF EXISTING SERVICE.

PP 5.0 WHAT LOADS DO EXISTING 100A AND 200A PANELS FEED?

PP 5.0 PROVIDE AVAILABLE GROUND FAULT CALCULATIONS. HOW DID YOU ARRIVE AT16464 AIC?
06/28/2011 ROBERT SHERRY WATER REVIEW Approved
06/28/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G.0 (BUILDING DATA); SHEET G0.1 (CODE SUMMARY): SHEET G.0 LISTS THE CONSTRUCTION TYPE AS VB, WHILE SHEET G0.1 INDICATES TYPE IIB. CLARIFY.
2. SHEET G0.1; CODE SUMMARY: IT IS INDICATED THAT A SERVICE SINK IS REQUIRED, BUT NONE IS PROVIDED. CLARIFY (INDICATED ON SEVERAL SHEETS).
3. SHEET D2.0; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE KEYNOTE REFERENCES ON PLAN.
4. SHEET A2.0: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE ENTIRE SHEET.
5. SHEET A2.0; FLOOR PLAN: THE CORRIDOR MUST BE FIRE RATED PER THE 2006 IBC, TABLE 1017.1.
6. SHEETS A2.3, A2.5, A2.6, A2.7 & A5.0: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
7. SHEET A8.0; WALL TYPES 2 AND 3: FOR THE METAL STUD BRACING AT THE TOP OF THE WALLS, PROVIDE DETAILS OF HOW THE BRACE CONNECTS TO THE EXISTING STRUCTURE, INDICATING QUANTITY AND SIZE OF CONNECTORS.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/28/2011 JASON GREEN ENGINEERING REVIEW Approved
06/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Provide a design for the support platform for the water heater and its connection to the building structure.
06/28/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Walls, ceiling and doors in rear exit cooridor must be rated per IFC Section 1017.
06/28/2011 ERIC NEWCOMB ADA REVIEW Passed
06/28/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/14/2011 CAGUILA1 WWM REVIEW Needs Review