Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02012
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/28/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROVIDE IECC LIGHTING CODE COMPLIANCE CERTIFICATE. PLEASE INDICATE LOCATION OF EXISTING SERVICE PP 5.0 PROVIDE CURRENT CAPACITY OF EXISTING SERVICE. PP 5.0 WHAT LOADS DO EXISTING 100A AND 200A PANELS FEED? PP 5.0 PROVIDE AVAILABLE GROUND FAULT CALCULATIONS. HOW DID YOU ARRIVE AT16464 AIC? |
06/28/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/28/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET G.0 (BUILDING DATA); SHEET G0.1 (CODE SUMMARY): SHEET G.0 LISTS THE CONSTRUCTION TYPE AS VB, WHILE SHEET G0.1 INDICATES TYPE IIB. CLARIFY. 2. SHEET G0.1; CODE SUMMARY: IT IS INDICATED THAT A SERVICE SINK IS REQUIRED, BUT NONE IS PROVIDED. CLARIFY (INDICATED ON SEVERAL SHEETS). 3. SHEET D2.0; DEMOLITION PLAN: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE KEYNOTE REFERENCES ON PLAN. 4. SHEET A2.0: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE ENTIRE SHEET. 5. SHEET A2.0; FLOOR PLAN: THE CORRIDOR MUST BE FIRE RATED PER THE 2006 IBC, TABLE 1017.1. 6. SHEETS A2.3, A2.5, A2.6, A2.7 & A5.0: THE CITY OF TUCSON REQUIRES THAT ALL LETTERING (UPPER AND LOWER CASE) BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 7. SHEET A8.0; WALL TYPES 2 AND 3: FOR THE METAL STUD BRACING AT THE TOP OF THE WALLS, PROVIDE DETAILS OF HOW THE BRACE CONNECTS TO THE EXISTING STRUCTURE, INDICATING QUANTITY AND SIZE OF CONNECTORS. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
06/28/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
06/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide a design for the support platform for the water heater and its connection to the building structure. |
06/28/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Walls, ceiling and doors in rear exit cooridor must be rated per IFC Section 1017. |
06/28/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
06/28/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/14/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |