Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02007
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2011 | DAVE MANN | FIRE | REVIEW | Denied | Unable to verify existence of panic hardware. (IFC 2006, section 1008.1.9) |
| 07/08/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Structural calculations do not analyize the existing evaporative cooler load plus the new evaporative cooler load bearing on the existing rigid steel beam span. Please provide analysis. END OF REVIEW |
| 07/11/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 07/11/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the terminations of the spray booth exhaust stacks are at least 3 feet above the existing evaporative coolers on the roof. Reference: Section 503.6.7, IFGC 2006. 2. Note 1 on sheet MP-1 refers to sheet SP-1 as having information regarding compliance with the requirements of Section 501.2.1, IMC 2006 for the location of the exhaust outlets but the only information shown is the distance from 2 of the 3 property lines to the exhaust outlets. Provide information to show that all of the requirements of Section 501.2.1, IMC 2006 have been met. 3. Clarify the scope of work. Sheet SP-1 calls for the installation of two spray booths and one mix room but other drawings call for the installation of six booths that are described as either prep booths or spray booths. 4. Provide the size of the existing evaporative cooler drains; verify that the existing drains are adequate for the new use. Reference: Section 102.4, IMC 2006. 5. The structural calculations for the installation of the new spray booths appear to address only the added load from the 6 new evaporative coolers on the existing purlins. How do the new exhaust fans affect the existing structure? How do the suspension cable loads (note 15, sheet SH-1) affect the existing structure? How does the combination of the new evaporative coolers, the existing evaporative coolers, and the suspension cable loads affect the moment frames for the building? Reference: Section 302.1, IMC 2006. |
| 07/11/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide freeze protection for the water piping located above the roof. Reference: Section 305.5, IPC 2006. 2. Clarify the natural gas demand for existing booth 7; it is shown as 7,000 CFH on the gas piping diagram on sheet MP-1. (Note: the governing code for natural gas piping in the City of Tucson shall be either the 2006 International Fuel Gas Code or the 2006 Uniform Plumbing Code.) |
| 07/20/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/24/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 08/24/2011 | SUE REEVES | REJECT SHELF | Completed |