Permit Number: T11CM01992
Parcel: 12704037B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01992
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 9); SHEET A3.1 (DETAIL 5): THE NEW WALL FOOTING IN THE N.E. CORNER SHOWS 1'-4" WIDE IN THE CALCS, 2'-0" WIDE ON SHEET S1.1, 1'-4" ON DETAIL 4/A3.1, AND 12" ON DETAIL 5. CLARIFY.
2. ADD STRUCTURAL MATERIAL NOTES FOR CONCRETE, STRUCTURAL STEEL, WELDING, REINFORCING, GLU LAMS, BOLTS, ETC.
3. ADD STRUCTURAL NOTES FOR LOADINGS (WIND, SEISMIC, ETC.) AND SOIL BEARING.
06/27/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/27/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
06/27/2011 ROBERT SHERRY WATER REVIEW Approved
06/27/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide roof drainage calculations and plans. Include the contribution of the enclosing parapets and the tower roof. Reference: Sections 1101.11 and 1106.0, UPC 2006.
06/27/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures,
06/27/2011 JASON GREEN ENGINEERING REVIEW Approved
11/07/2011 GBONILL1 ZONING REVIEW Needs Review
11/07/2011 GBONILL1 FIRE REVIEW Needs Review