Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01957
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Drawing to structural calculation very confusing. a. Please add key plan to structural calculations. b. Please add roof framing plan to drawings. Insure structural engineer's seal on all structural details sheets. 2. Details on drawings are not referenced properly i.e. details 8/A4.1 and 2/A4.1. Please connect these details to the building sections. 3. Special Inspection Certifications are not included with this submittal, please provide. END OF REVIEW |
| 09/27/2011 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 09/27/2011 | SREEVES1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/27/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |