Permit Number: T11CM01951
Parcel: 14126006H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01951
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2011 TERRY STEVENS ZONING REVIEW Passed
06/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. revise the ventilation calculation for AC-1. The lobby is best described as a lobby for a public assembly space; not a main entry lobby for an office building (Table 6-1, ASHRAE 62.1-2004)
2. Provide auxiliary drain pans or secondary drain systems for the fan coil unit FC-1. Reference: Section 307.2.3 IMC 2006.
3. Revise the envelope energy calculation to correspond to the building construction shown on the plans.
06/23/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/23/2011 ROBERT SHERRY WATER REVIEW Approved
06/23/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheet A6.0

1. Show door hardware on plans. Comply with IFC Chapt. 10.
06/23/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
06/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information regarding the rest of the existing gas piping system to ensure that it won't beoverloaded by the new addition..
06/23/2011 LOREN MAKUS ENGINEERING REVIEW Approved
06/24/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2011 ERIC NEWCOMB ADA REVIEW Passed
06/24/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed