Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM01911
Parcel: 10926009E

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM01911
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 DAVE MANN FIRE REVIEW Approved
07/01/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied MINIMUM FONT SIZE TO BE 3/32" ON ALL PLAN SHEETS (PP E1.2 , E1.3)

WIRE SIZES FROM TRHASITION BOX TO INVERTER ARE NOT COORDINATED BETWEEN 1-LINE AND 3-LINE DRAWINGS. DO YOU WANT #10 OR #8 AWG WIRES?

PLEASE CLARIFY WHY YOU'VE NOTED A 1200 AMP BUS INSIDE THE 2000 A SERVICE
07/01/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PLEASE NOTE ON PP L1.0 WHICH BUILDING IS WHICH OR PROVIDE CUT REFERENCE TO CORRECT PAGES.

CLARIFY ELEVATION VIEWS AND ENSURE THAT KEYNOTES ARE CLEARLY CONNECTED TO APPROPRIATE ELEVATION (THERE ARE 2 EACH SOUTH AND WEST ELEVATION VIEWS ON L-1.2 AND BOTH ELEVATION PAGES HAVE A "DETAIL #" WHICH DOES NOT MATCH DETAIL NUMBER LISTED WITH ELEVATION)

PROVIDE ALL INFORMATION FOR ROOF MOUNTS, RACKING ASSEMBLY, UPLIFT CALCULATIONS, ETC FOR SCIENCE & TECHNOLOGY BUILDING.

WHAT DOES KEYNOTE 7 PP L-1.2 REFERENCE?

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
07/07/2011 SUE REEVES REJECT SHELF Completed