Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T11CM01911
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/01/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | MINIMUM FONT SIZE TO BE 3/32" ON ALL PLAN SHEETS (PP E1.2 , E1.3) WIRE SIZES FROM TRHASITION BOX TO INVERTER ARE NOT COORDINATED BETWEEN 1-LINE AND 3-LINE DRAWINGS. DO YOU WANT #10 OR #8 AWG WIRES? PLEASE CLARIFY WHY YOU'VE NOTED A 1200 AMP BUS INSIDE THE 2000 A SERVICE |
| 07/01/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PLEASE NOTE ON PP L1.0 WHICH BUILDING IS WHICH OR PROVIDE CUT REFERENCE TO CORRECT PAGES. CLARIFY ELEVATION VIEWS AND ENSURE THAT KEYNOTES ARE CLEARLY CONNECTED TO APPROPRIATE ELEVATION (THERE ARE 2 EACH SOUTH AND WEST ELEVATION VIEWS ON L-1.2 AND BOTH ELEVATION PAGES HAVE A "DETAIL #" WHICH DOES NOT MATCH DETAIL NUMBER LISTED WITH ELEVATION) PROVIDE ALL INFORMATION FOR ROOF MOUNTS, RACKING ASSEMBLY, UPLIFT CALCULATIONS, ETC FOR SCIENCE & TECHNOLOGY BUILDING. WHAT DOES KEYNOTE 7 PP L-1.2 REFERENCE? |