Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 DAVE MANN FIRE REVIEW Approved
07/01/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied MINIMUM FONT SIZE TO BE 3/32" ON ALL PLAN SHEETS (PP E1.2 , E1.3)

WIRE SIZES FROM TRHASITION BOX TO INVERTER ARE NOT COORDINATED BETWEEN 1-LINE AND 3-LINE DRAWINGS. DO YOU WANT #10 OR #8 AWG WIRES?

PLEASE CLARIFY WHY YOU'VE NOTED A 1200 AMP BUS INSIDE THE 2000 A SERVICE
07/01/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PLEASE NOTE ON PP L1.0 WHICH BUILDING IS WHICH OR PROVIDE CUT REFERENCE TO CORRECT PAGES.

CLARIFY ELEVATION VIEWS AND ENSURE THAT KEYNOTES ARE CLEARLY CONNECTED TO APPROPRIATE ELEVATION (THERE ARE 2 EACH SOUTH AND WEST ELEVATION VIEWS ON L-1.2 AND BOTH ELEVATION PAGES HAVE A "DETAIL #" WHICH DOES NOT MATCH DETAIL NUMBER LISTED WITH ELEVATION)

PROVIDE ALL INFORMATION FOR ROOF MOUNTS, RACKING ASSEMBLY, UPLIFT CALCULATIONS, ETC FOR SCIENCE & TECHNOLOGY BUILDING.

WHAT DOES KEYNOTE 7 PP L-1.2 REFERENCE?