Permit Number: T11CM01902
Parcel: 13329015B

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T11CM01902
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2011 ANDREW CONNOR LANDSCAPE REVIEW Denied
10/13/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/13/2011

The project can not be approved at this time. Address the following comments and provide a detailed response letter with the next submittal:

1. Provide, on the site plan, the site finish grades/spot elevations (D.S. 2-02.2.1.A.16).
2. The estimated cut and fill quantities. If the cut and/or fill quantities are zeros, provide this information on the cover sheet (D.S. 2-02.2.1.A.17).
3. Provide, on the site plan, the radii and dimensions of the back-up spur (D.S. 3-05.2.2.D).


Resubmittal Required: Revised Site Plan