Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM01902
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire sprinklers required due to distance from fire hydrants and lack of Fire Department access. Refer to C.O.T amendments to the 2006 IFC, section 508.5.1. |
| 06/29/2011 | TERRY STEVENS | ZONING | REVIEW | Denied | 06/29/2011 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
| 06/30/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T1.1 (PARKING CALCULATIONS); SHEET AS1.1 (SITE PLAN): THE PARKING CALCULATIONS INDICATE 48 SPACES PROVIDED WITH 2 HANDICAP SPACES FOR THE ENTIRE SITE. THE SITE PLAN DOES NOT INDICATE THE SAME. VERIFY. 2. SHEET T1.1; CODE ANALYSIS (MINIMUM PLUMBING FACILITIES): THE DRAWING INDICATES ONLY ONE WATER CLOSET IS REQUIRED AND PROVIDED. IBC TABLE 2902.1 AND SECTION 2902.2 INDICATE SEPARATE FACILITIES FOR EACH SEX ARE REQUIRED. VERIFY. IBC SECTION 2902.4.1 MAY BE USED, BUT THIS SHOULD BE ADDRESSED ON THE DRAWINGS. 3. SHEET AS1.1; SITE PLAN: NO HANDICAP PARKING SPACE, ACCESS AISLE, OR RAMP ARE INDICATED FOR THE NEW ADDITION. VERIFY. 4. SHEET S1.4 (SHEAR WALL SCHEDULE); STRUCTURAL CALCULATIONS (SHEET 25): THE CALCULATIONS INDICATE 5/8" DIAMETER ANCHOR BOLTS IN THE SHEAR WALLS, WHILE THE SCHEDULE INDICATES 1/2" DIAMETER ANCHOR BOLTS. CLARIFY. 5. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE OR LEERAY HANLY BEFORE THOSE SUBMITTALS WILL BE REVIEWED. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/06/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED ADDRESSING REVIEW- SEPARATE LOT NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER |
| 07/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide energy code compliance calculations for the building envelope using the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. |
| 07/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the inverts and slope of the building sewer line on drawing. Reference: Section 106.3.1, IPC 2006. 2. Coordinate the location of the water service entrance to the building with the civil site plan. Reference: Section 106.3.1, IPC 2006. 3. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for educational occupancy (i.e. separate facilities for each sex). |
| 07/08/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Verify the size of the proposed water meter (3/4") is available from Tucson Water. 2. Show the location of the proposed reduced pressure backflow preventer (RPBP). Reference: Section 106.3.1 IPC 2006. |
| 07/14/2011 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 07/14/2011, The building plan can not be approved until the site plan is approved. |
| 07/15/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/22/2011 | GERARDO BONILLA | REJECT SHELF | Completed |