Permit Number: T11CM01902
Parcel: 13329015B

Review Status: Completed

Review Details: SITE

Permit Number - T11CM01902
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2011 MARTIN BROWN FIRE REVIEW Approved
06/24/2011 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T11CM01902
8655 E. Broadway Blvd.
Site Plan

TRANSMITTAL DATE: 06/27/11

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site contains two (2) separate parcels therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide a Pima County Tax Parcel Combo.
2. Please reference the last approved site plan (T00CM02983) by adding the permit number near the lower right corner of all sheets.

3. In the code analysis portion of sheet T1.1, the zoning of the property is incorrect it should be C-1. Revise.

In the same portion of sheet T1.1 revise the existing use to read as follows: Dare Care "34"

Provide the allowed Floor Area Ratio (FAR) which is 2.00.

The indicated required front street setback is incorrect. The required front setback is 21' or the height of the structure from the back of future curb. Revise.

Provide the allowed building height (75') in the calculations.

4. The parking calculations are incorrect as far as the number of required parking spaces. There has been a change to the LUC as far as number of required parking spaces. The new calculation for a Day Care use is 1 spaces per 300 sq. ft. of gross floor area. Revise calculations.

5. The zoning of the adjoining properties is C-1. Revise site plan.

6. Provide the setback from the proposed building to the west property line.

7. On the site plan the indicated square footage of 11,320 on the foot print of the existing structure is incorrect. Should be 8,180 sq.ft. Revise.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T11CM01902.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/29/2011 LEERAY HANLY H/C SITE REVIEW Approved
07/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location of the water meter
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of the upstream and downstream manholes or cleanouts
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 106.3.1, IPC 2006.
07/13/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 07/14/2011

Provide the following information on the site plan:

1. The existing and future sight visibility triangles including their dimensions (D.S. 2-02.2.1.A.10).
2. The width of driveways and parking area access lanes (PAALs) (D.S. 2-02.2.1.A.11).
3. Vehicular, bicycle, pedestrian, and handicapped circulation clearly identified (D.S. 2-02.2.1.A.12).
4. Site drainage patterns including the roof drainage, the building finish floor elevation and the site finish grades (D.S. 2-02.2.1.A.16).
5. The estimated cut and fill quantities (D.S. 2-02.2.1.A.17).
6. Dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way (D.S. 2-02.2.1.A.19).
7. All easements of record must be graphically shown on the plan together with recording docket and page reference (D.S. 2-02.2.1.A.20).
8. Dimensions from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines (D.S. 2-02.2.1.A.21).
9. Existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number (D.S. 2-02.2.1.A.23).
10. Fences, walls, or vegetation for screening by type, material, height, location, and spacing (D.S. 2-02.2.1.A.27).
11. Legends and symbols used in the preparation of the site plan shall be in accordance with City of Tucson Drafting Standards. (D.S. 2-02.2.1.B).


Resubmittal Required: Revised Site Plan
07/21/2011 ANDREW CONNOR NPPO REVIEW Approved
07/21/2011 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Submit previously approved landscape plans for reference.

2. Landscaping requirements apply to expansion of existing development as follows:

" On sites where the gross floor area of the existing building(s) is more than ten thousand (10,000) square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:

" If the expansion is less than 25%, the requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B

" If the expansion is 25% or greater or if expansions as of February 15, 1991 cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the requirements of this Division apply to the entire site per LUC 3.7.1.2.B. Provide expansion calculations

3. If necessary submit a landscape plan with the following information:


4. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. On streets designated as Major Streets and Routes (MS&R), the street landscape border is measured from the MS&R right-of-way line as determined by LUC 2.8.3.4.

5. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4

6. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4.


7. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g.


8. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I

9. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

10. Planting Plan. The planting plan and layout calculations will include the following information:

" The location of individual plants one (1) gallon or larger.

" Sizes of plants indicated in boxes, gallon cans

" Ultimate size of plants indicated by the spread of canopy, circumference of shrubs, or spread of ground cover.

" Both the proper and common name of each type of plant material.

" Location, size, and name of existing vegetation to remain in place.

" Material and areas of inert ground cover.

11. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

12. All landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.

13. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

14. Additional comments may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2011 GERARDO BONILLA REJECT SHELF Completed