Permit Number: T11CM01896
Parcel: 13507451C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01896
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2011 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T11CM01896
1851 South Pantano Road
Building plans for D11-0016


TRANSMITTAL: July 19, 2011


COMMENTS: Please attach a response letter with the next submittal.

Development Plan D11-0016 must be approved prior to approval of building plans.
07/21/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/01/2011 ROBERT SHERRY WATER REVIEW Approved
08/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; the submitted calculations do not appear to be for the shell addition built under activity T11CM01550. [Original comment: Provide energy code compliance calculations for the building envelope (using the climate zone for Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
2. Comment not resolved; no information has been presented to verify that the existing roof is capable of supporting the new mechanical equipment. [Original comment: The proposed rooftop heat pump units are not shown in the same locations as they were on roof framing plan of the shell package. Verify that the existing roof is capable of supporting the roof top units. Reference: Section 302.1, IMC 2006.]
08/02/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01896
1851 S Pantano Rd

Elecrtrical plans denied for following:

1. The five FC units shown on sheet E2.1 are not listed in the panel schedule for OLB, the loads have not been inserted and totaled.
2. Last submittal did not indicate the new 112.5 KVA
transformer on the roof, this will require
a structrual detail for the verification of roof support, should be per Structual Engineer.

Ray T Majuta,
Elect Pln Ck,PDSD,
City of Tucson
8/3/11