Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T11CM01884
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2011 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Passed | |
| 06/20/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/30/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. DRAWINGS MUST BE STAMPED BY A LICENSED PROFESSIONAL. |
| 07/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM01884 333 E Wetmore Rd Verizon Cell Site (Emergency Generator Install) The electrical plans have been denied for the following: 1. The plans need to be sealed by an EE. 2. Provide size of generator,voltage amperage etc. 3. Provide specification sheet on transfer switch. 4. Conductor sizes going from generator to transfer switch,to existing source need to be provided. 5.Show Fault current available at existing service tapping into, and verify FC for transfer sw. 6. Provide grounding at generator on drawing. 7. Where will the heater and charger circuits tie into,where will the control circuits tie into. 8. The address provided is the general address for the building,the permit needs to have the address for the meter for the cell site service. Ray Majuta, Elect Pln Ck,PDSD, City of Tucson, 7/7/11 Ray.majuta@tucsonaz.gov |
| 07/13/2011 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T11CM01884 333 E. Wetmore Road (1st Review) TRANSMITTAL DATE: July 13, 2011 1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning cannot approve the plan until all other PDSD agencies have approved the plan. Once all other PDSD agencies have approved Zoning is available for an over the counter review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\celltower\t11cm01844.doc |
| 07/13/2011 | MICHAEL WYNEKEN | PLANNING-CITY HALL | REVIEW | Denied | Add the following general notes to the site plan (Sheet Z-1): 1. The generator shall operate up to 45 minutes per week for testing and diagnostics. 2. Testing of the generator shall occur between the hours of 9:00 AM and 4:00 PM. 3. Generator operations shall comply with Section 16-31 Excessive Noise, of the Tucson City Code. 5. The proposed generator pad shall be within an eight-foot high enclosure painted with graffiti resistant paint to match the existing structures/walls on the property. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/19/2011 | SUE REEVES | REJECT SHELF | Completed |