Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01880
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/21/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide information regarding the fume hood operation to show that the design meets the requirements of Sections 501.2, 501.3, 502.1, and 510, IMC 2006. |
| 06/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Citing a preference by the occupant to avoid saw-cutting the slab as justification for the use of a sump pump to drain the new sink is insufficient. Provide a gravity drain for the sink. |
| 07/14/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |