Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01880
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/16/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information regarding the fume hood operation to show that the design meets the requirements of Sections 501.2, 501.3, 502.1, and 510, IMC 2006. 2. Provide justification for the use of the ventilation rate for a storage area in a room described as an equipment assembly (i.e. factory) area. Reference Section 403.3, IMC 2006. |
| 06/16/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Exit sign shown to remain (keynote 7 pp e1.0) is in front of what will be a blocked door. What products of assembly are being used? Please provide information on as to whether the assembly area is a classified location. Show location of new generator Provide cutsheets for new generator Provide more information on ATS. Is it 4 or 3 wire disconnecting? Clarify grounding of generator if ATS is 3 wire disconnnecting. Clarify disconnect type and location at generator errata: notes for generator indicate 120/208v-#(phase)-4W should read ...-3(phase)- Justify 10 Kaic rating of panel P3 (what is available from generator) |
| 06/16/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/16/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. HOW IS THIS BUILDING CLASSIFIED AS A B OCCUPANCY? IT APPEARS THERE ARE EQUIPMENT ASSEMBLY AREAS (F OCCUPANCY?). VERIFY. 2. IT IS NOTED THAT THERE IS AN EXISTING DRINKING FOUNTAIN IN THE BUILDING. LOCATE ON THE PLAN. 3. INTERIOR WALLS MUST BE BRACED TO RESIST HORIZONTAL LOADS OF 5 PSF PER IBC SECTION 1607.13. PROVIDE A DETAIL INDICATING BRACE SIZES AND SPACING, HOW THE BRACES ATTACH TO THE EXISTING STRUCTURE ABOVE, AND HOW THE BRACES ATTACH TO THE TOP OF THE WALL. 4. IBC SECTION 1014 INDICATES EXIT SHALL NOT PASS THROUGH ACCESSORY AREAS THAT ARE HIGH HAZARD OCCUPANCY. ACCESS TO THE SECOND EXIT PASSES THROUGH AN EQUIPMENT ASSEMBLY AREA, AND A LOADING AREA. A DISCERNIBLE PATH MUST ALSO BE PROVIDED. COMMENT ON THESE POINTS. |
| 06/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide justification for the use of a sump pump to drain the new sink rather than using a gravity drain. |
| 06/16/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/16/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 06/21/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 06/21/2011 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 06/21/2011 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review |