Permit Number: T11CM01877
Parcel: 106101310

Address:
3975 N MILLER AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01877
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheet A01

1. Provide approved Building Official Petition.
2. Show location of nearest fire hydrant.

Sheet A11

1. Provide approved Building Official Petition or provide panic hardware at exits.
2. Follow Tucson Codes, project is not in Oro Valley.
06/28/2011 GERRY KOZIOL WWM REVIEW Passed
07/06/2011 DAVID RIVERA ZONING REVIEW Denied T11CM01877
3975 N. Miller Ave.
Museum Ue (Cultural)
Site Plan

From: David Rivera
Principal Planner
Zoning Review Section


Comments:

The plan has to be reviewed by zoning and while the plan matches or complies with the site plan depiction the building plans cannot be approved until the site plan is approved.
07/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A01; BUILDING CODE SUMMARY: REVISE THE INFORMATION PER THE BUILDING OFFICIAL'S RESPONSE TO THE APPEAL. THE OCCUPANCY CLASSIFICATION SHOULD BE A-3. THE NET AREA SHOULD BE 5908 SF (TOTAL AREA IS STILL 7642 SF). THE OCCUPANT LOAD SHOULD REFERENCE TABLE 1004.1.1, USE 50 SF/OCCUPANT (NET), AND AN ALLOWABLE OCCUPANT LOAD OF 118.
2. SHEET A01; BUILDING CODE SUMMARY: REVISE THE REQUIRED EXIT WIDTH FOR THE NEW OCCUPANT LOAD.
3. SHEET A01; BUILDING CODE SUMMARY: THE TYPE OF CONSTRUCTION IS NOTED AS VB (EXISTING ENGINEERED BUILDING). PER THE 2006 IBC SECTION 602.2, THIS SHOULD FALL UNDER A II-B CONSTRUCTION CLASSIFICATION. VERIFY.
4. SHEET A11; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL CALL-OUTS ON THE PLAN.
5. SHEET A11; FLOOR PLAN: INDICATE THE SINGLE POINT-OF-USE WATER DISPENSER AND THE SERVICE SINK ON THE DRAWING.
6. SHEETS A11 AND A12; GENERAL NOTES: NOTE "A" REFERENCES ORO VALLEY. REVISE.
7. SHEETS A11 AND A12; GENERAL NOTES: NOTE "E" INDICATES TO "CAULK PLUMBING FIXTURES". IS THIS A REFERENCE TO EXISTING FIXTURES? CLARIFY.
8. SHEET A12; FLOOR PLAN: PER THE 2006 IBC SECTION 1008.1.2, THE DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE. VERIFY AND REVISE AS REQUIRED AT D01.
9. SHEET A12; DOOR SCHEDULE, DOOR AND FRAME ELEVATIONS, HEAD AND JAMB DETAILS: CHANGE THE SHEET REFERENCE FROM A61 TO A12.
10. SHEET A12; DOOR SCHEDULE: PROVIDE REMARKS AND/OR SPECIFICATIONS CONCERNING HARDWARE HW1 AND HW2.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/07/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/11/2011 ROBERT SHERRY WATER REVIEW Denied Show the location and size of the reduced pressure backflow preventer for the building water service.
07/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved