Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01877
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Sheet A01 1. Provide approved Building Official Petition. 2. Show location of nearest fire hydrant. Sheet A11 1. Provide approved Building Official Petition or provide panic hardware at exits. 2. Follow Tucson Codes, project is not in Oro Valley. |
| 06/28/2011 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/06/2011 | DAVID RIVERA | ZONING | REVIEW | Denied | T11CM01877 3975 N. Miller Ave. Museum Ue (Cultural) Site Plan From: David Rivera Principal Planner Zoning Review Section Comments: The plan has to be reviewed by zoning and while the plan matches or complies with the site plan depiction the building plans cannot be approved until the site plan is approved. |
| 07/07/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A01; BUILDING CODE SUMMARY: REVISE THE INFORMATION PER THE BUILDING OFFICIAL'S RESPONSE TO THE APPEAL. THE OCCUPANCY CLASSIFICATION SHOULD BE A-3. THE NET AREA SHOULD BE 5908 SF (TOTAL AREA IS STILL 7642 SF). THE OCCUPANT LOAD SHOULD REFERENCE TABLE 1004.1.1, USE 50 SF/OCCUPANT (NET), AND AN ALLOWABLE OCCUPANT LOAD OF 118. 2. SHEET A01; BUILDING CODE SUMMARY: REVISE THE REQUIRED EXIT WIDTH FOR THE NEW OCCUPANT LOAD. 3. SHEET A01; BUILDING CODE SUMMARY: THE TYPE OF CONSTRUCTION IS NOTED AS VB (EXISTING ENGINEERED BUILDING). PER THE 2006 IBC SECTION 602.2, THIS SHOULD FALL UNDER A II-B CONSTRUCTION CLASSIFICATION. VERIFY. 4. SHEET A11; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WALL CALL-OUTS ON THE PLAN. 5. SHEET A11; FLOOR PLAN: INDICATE THE SINGLE POINT-OF-USE WATER DISPENSER AND THE SERVICE SINK ON THE DRAWING. 6. SHEETS A11 AND A12; GENERAL NOTES: NOTE "A" REFERENCES ORO VALLEY. REVISE. 7. SHEETS A11 AND A12; GENERAL NOTES: NOTE "E" INDICATES TO "CAULK PLUMBING FIXTURES". IS THIS A REFERENCE TO EXISTING FIXTURES? CLARIFY. 8. SHEET A12; FLOOR PLAN: PER THE 2006 IBC SECTION 1008.1.2, THE DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE. VERIFY AND REVISE AS REQUIRED AT D01. 9. SHEET A12; DOOR SCHEDULE, DOOR AND FRAME ELEVATIONS, HEAD AND JAMB DETAILS: CHANGE THE SHEET REFERENCE FROM A61 TO A12. 10. SHEET A12; DOOR SCHEDULE: PROVIDE REMARKS AND/OR SPECIFICATIONS CONCERNING HARDWARE HW1 AND HW2. 11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/07/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 07/11/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location and size of the reduced pressure backflow preventer for the building water service. |
| 07/11/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/11/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/18/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |