Permit Number: T11CM01877
Parcel: 106101310

Address:
3975 N MILLER AV

Review Status: Completed

Review Details: SITE

Permit Number - T11CM01877
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2011 DAVE MANN FIRE REVIEW Denied
07/06/2011 DAVID RIVERA ZONING REVIEW Denied T11CM01877
3975 N. Miller Ave.
Museum Ue (Cultural)
Site Plan

From: David Rivera
Principal Planner
Zoning Review Section


Comments: The plan has to be revised to include the following data.

a. Revise the Existing and proposed use notes to include "Civic USE Group" and the land use group should be revised to Cultural - Museum.

b. The parking calculations have been listed based on the revised ratios at 1 space per 300 GFA. When an if using the new ratios the new bicycle parking ratios must be used as well and the number of facilities must be provided per the new ratios. Draw, label and dimension the required facilities. Include any bicycle facilities detail drawings necessary. List the bicycle parking requirement under the Zoning data information section.

c. List the loading zone requirements under the Zoning data section.

d. Curb access ramps and truncated domes may be required at connection points from the cross walks connecting to the accessible pedestrian system to the caboose exhibit. See the ADA review comments for information on this requirement.

e. Label the width of the new sidewalk area between the storage container and the new exhibit building.

f. Label the width of the painted crosswalks.

The zoning comments are minor and zoning is willing to re-review this plan over the counter with an appointment made ahead of time. If the applicant wishes to have this plan reviewed over the counter please call for an appointment otherwise the plan must be re-submitted for review.
07/07/2011 RONALD BROWN H/C SITE REVIEW Denied 1. Please provide large scale details for both accessible parking layouts showing all dimensions, slopes, signage, ramps, detectable warnings as required, aisles, international symbols and connection to accessible route.
a. One of the accessible parking spaces is to be "Van Accessible", please identify it.
2. For the two new marked crossings:
a. Provide detectable warnings at both crossings at both ends of crossings.
b. Insure slope compliance with ICC/ANSI 117.1, Section 403.3.
3. Provide a large scale signage detail including "Van Accessible" signage.
4. Insure all slopes for new accessible routes comply with ICC/ANSI 117.1, Section 403.3.
END OF REVIEW
07/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location, invert, and rim elevation of the upstream and downstream manholes
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
07/21/2011 ANDREW CONNOR LANDSCAPE REVIEW Denied Submit previously approved landscape plans for reference. If no plan exists then provide the location, size, and name of existing vegetation to remain in place, including both the proper and common name of each type of plant material on the site plan.
07/21/2011 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2011 CINDY AGUILAR OUT TO CUSTOMER Completed