Permit Number: T11CM01867
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01867
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2011 STEVE SHIELDS ZONING REVIEW Approved
06/14/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
06/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments:
1. Sheet E1.1 shows circuits 37,39 for AHU, and 33,35 for CU, correct these in panel schedule.
2. Cannot locate circuits 17 and 23.


Ray Majuta
Elect Pln Ck
6/14/11
06/14/2011 ROBERT SHERRY WATER REVIEW Approved
06/14/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.2; CASH WRAP PLANS: ALL ELEVATIONS REFER TO SHEET A2.1. VERIFY.
2. SHEET A3.1; DETAILS 1, 2, AND 3: PROVIDE METAL FRAMING SIZES, SPACING, AND CONNECTIONS. "AS REQUIRED" IS NOT ADEQUATE.
3. GEMERAL: PROVIDE A NOTE ON THE PLANS DESCRIBING THE DISTANCE TO THE DRINKING FOUNTAINS AND RESTROOM FACILITIES, AND THAT THOSE DISTANCES MEET IBC SECTION 2902 REQUIREMENTS.
06/14/2011 JASON GREEN ENGINEERING REVIEW Approved
06/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a design for the collection of the condensate drainage. Indirect waste receptors may not be installed behind access doors.
06/14/2011 DAVE MANN FIRE REVIEW Approved
06/14/2011 ERIC NEWCOMB ADA REVIEW Passed 1. SHEET A2.2; CASH WRAP PLANS: ALL ELEVATIONS REFER TO SHEET A2.1. VERIFY.
2. SHEET A3.1; DETAILS 1, 2, AND 3: PROVIDE METAL FRAMING SIZES, SPACING, AND CONNECTIONS. "AS REQUIRED" IS NOT ADEQUATE.
3. GEMERAL: PROVIDE A NOTE ON THE PLANS DESCRIBING THE DISTANCE TO THE DRINKING FOUNTAINS AND RESTROOM FACILITIES, AND THAT THOSE DISTANCES MEET IBC SECTION 2902 REQUIREMENTS.
06/14/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/16/2011 GBONILL1 WWM REVIEW Needs Review