Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01867
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006. |
06/14/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical comments: 1. Sheet E1.1 shows circuits 37,39 for AHU, and 33,35 for CU, correct these in panel schedule. 2. Cannot locate circuits 17 and 23. Ray Majuta Elect Pln Ck 6/14/11 |
06/14/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/14/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.2; CASH WRAP PLANS: ALL ELEVATIONS REFER TO SHEET A2.1. VERIFY. 2. SHEET A3.1; DETAILS 1, 2, AND 3: PROVIDE METAL FRAMING SIZES, SPACING, AND CONNECTIONS. "AS REQUIRED" IS NOT ADEQUATE. 3. GEMERAL: PROVIDE A NOTE ON THE PLANS DESCRIBING THE DISTANCE TO THE DRINKING FOUNTAINS AND RESTROOM FACILITIES, AND THAT THOSE DISTANCES MEET IBC SECTION 2902 REQUIREMENTS. |
06/14/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
06/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a design for the collection of the condensate drainage. Indirect waste receptors may not be installed behind access doors. |
06/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
06/14/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | 1. SHEET A2.2; CASH WRAP PLANS: ALL ELEVATIONS REFER TO SHEET A2.1. VERIFY. 2. SHEET A3.1; DETAILS 1, 2, AND 3: PROVIDE METAL FRAMING SIZES, SPACING, AND CONNECTIONS. "AS REQUIRED" IS NOT ADEQUATE. 3. GEMERAL: PROVIDE A NOTE ON THE PLANS DESCRIBING THE DISTANCE TO THE DRINKING FOUNTAINS AND RESTROOM FACILITIES, AND THAT THOSE DISTANCES MEET IBC SECTION 2902 REQUIREMENTS. |
06/14/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/16/2011 | GBONILL1 | WWM | REVIEW | Needs Review |