Permit Number: T11CM01858
Parcel: 11703321C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01858
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
06/16/2011 GERRY KOZIOL WWM REVIEW Approved
06/16/2011 MICHAEL ST. PAUL ZONING_HISTORIC REVIEW Approved
06/20/2011 DAVE MANN FIRE REVIEW Approved
06/23/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; APPLICABLE CODES: REVISE THE ADA NOTE. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003.
2. SHEET S1.4; JOIST SCHEDULE: IS THE REMARK ON J5 CORRECT? SHOULD THIS BE "SEE NOTE 1"? VERIFY.
3. SHEET S1.4 (COLUMN SCHEDULE); STRUCTURAL CALCULATIONS (SHEETS 35 AND 36): THE CALCULATION ON SHEET 36 USES A HSS 6X4X3/16 FOR THE DESIGN, WHILE THE DRAWING INDICATES 2-C6X8.2. VERIFY.
4. SHEET S5.1; DETAIL 212: THE EPOXY BOLT NOTE INDICATES BOLTS TO BE ANGLED, BUT THE DETAIL DOES NOT INDICATE THAT. CLARIFY.
5. SHEET A2.1; KEYNOTES: REVISE NOTES 3, 16, AND 17. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003.
6. SHEET A2.2; KEYNOTES: REVISE NOTES 1, 4, 5, 6, 7, 8, AND 9. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003.
7. SHEET A2.2; ENLARGED FLOOR PLAN; ELEVATION 6: THE TRANSFER-TYPE SHOWER REQUIRES A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 608.5.1. REVISE THE ELEVATION.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listed and labeled fire dampers for protection of ducts and penetrations of fire resistive walls (e.g. FC-3 supply, penetrating duct greater than 100 square inches). Reference: Section 607.5.3, IMC 2006.
06/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A church is classified as Assembly, A-3; revise the water fixture unit calculations accordingly.
2. Clarify the labeling on the waste and vent riser diagram; the mop sink appears to be called out as a shower trim (P10).
3. Indirect waste receptors shall not be installed in unventilated spaces (e.g. floor sinks in closets). Reference: Section 802.3, IPC 2006.
06/29/2011 ROBERT SHERRY WATER REVIEW Approved
07/01/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
07/07/2011 SUE REEVES REJECT SHELF Completed