Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01858
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/16/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/16/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/16/2011 | MICHAEL ST. PAUL | ZONING_HISTORIC | REVIEW | Approved | |
06/20/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
06/23/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; APPLICABLE CODES: REVISE THE ADA NOTE. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003. 2. SHEET S1.4; JOIST SCHEDULE: IS THE REMARK ON J5 CORRECT? SHOULD THIS BE "SEE NOTE 1"? VERIFY. 3. SHEET S1.4 (COLUMN SCHEDULE); STRUCTURAL CALCULATIONS (SHEETS 35 AND 36): THE CALCULATION ON SHEET 36 USES A HSS 6X4X3/16 FOR THE DESIGN, WHILE THE DRAWING INDICATES 2-C6X8.2. VERIFY. 4. SHEET S5.1; DETAIL 212: THE EPOXY BOLT NOTE INDICATES BOLTS TO BE ANGLED, BUT THE DETAIL DOES NOT INDICATE THAT. CLARIFY. 5. SHEET A2.1; KEYNOTES: REVISE NOTES 3, 16, AND 17. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003. 6. SHEET A2.2; KEYNOTES: REVISE NOTES 1, 4, 5, 6, 7, 8, AND 9. ACCESSIBILITY REQUIREMENTS FOLLOW THE 2006 IBC AND ICC/ANSI A117.1-2003. 7. SHEET A2.2; ENLARGED FLOOR PLAN; ELEVATION 6: THE TRANSFER-TYPE SHOWER REQUIRES A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 608.5.1. REVISE THE ELEVATION. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
06/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide listed and labeled fire dampers for protection of ducts and penetrations of fire resistive walls (e.g. FC-3 supply, penetrating duct greater than 100 square inches). Reference: Section 607.5.3, IMC 2006. |
06/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A church is classified as Assembly, A-3; revise the water fixture unit calculations accordingly. 2. Clarify the labeling on the waste and vent riser diagram; the mop sink appears to be called out as a shower trim (P10). 3. Indirect waste receptors shall not be installed in unventilated spaces (e.g. floor sinks in closets). Reference: Section 802.3, IPC 2006. |
06/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/01/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/07/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
07/07/2011 | SUE REEVES | REJECT SHELF | Completed |