Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/09/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
06/09/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
06/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed. Provide waste and vent isometrics; clarify the stand pipe and how it relates to the dishwasher. Reference: Section 103.2.3, UPC 2006. |
06/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the new scope of work. Are the new fan coils replacing similar fan coils? How are the new fan coils connected to the building structure; are the condensate drains existing? 2. Specify the new supply fan, SF-1 (or is it specified as EF-1). 3. Provide balancing data for the FC-1 serving the reception, office and conference room. (Are there really two FC-1 units?) |
06/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/24/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |