Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM01784
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01784
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2011 DAVID RIVERA ZONING REVIEW Approved
06/09/2011 LOREN MAKUS ENGINEERING REVIEW Approved
06/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Provide waste and vent isometrics; clarify the stand pipe and how it relates to the dishwasher. Reference: Section 103.2.3, UPC 2006.
06/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the new scope of work. Are the new fan coils replacing similar fan coils? How are the new fan coils connected to the building structure; are the condensate drains existing?
2. Specify the new supply fan, SF-1 (or is it specified as EF-1).
3. Provide balancing data for the FC-1 serving the reception, office and conference room. (Are there really two FC-1 units?)
06/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2011 CPIERCE1 WWM REVIEW Needs Review