Permit Number: T11CM01784
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01784
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2011 MARTIN BROWN FIRE REVIEW Approved
06/07/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/07/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments:

1. Relocated water heater, where is this circuit connected at ?
2. Mechanical Sheet M-3 shows 4 new FC units, provide information on these,where connected, are they replacement units,will same circuits be used ?
3. New ex fan sheet M-3,where is this located on electrical plan.

Ray Majuta,
Elect Pln Ck,
PDSD, Tucson
Ray.majuta@tucsonaz.gov
06/07/2011 ROBERT SHERRY WATER REVIEW Approved
06/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS G-1, A-1-REV, A-2-REV, AND A-4 ARE ALL MARKED AS "PRELIMINARY NOT FOR CONSTRUCTION". REVISE.
06/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide waste and vent isometrics; clarify the stand pipe and how it relates to the dishwasher. Reference: Section 103.2.3, UPC 2006.
06/07/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/07/2011 ERIC NEWCOMB ADA REVIEW Passed
06/09/2011 CPIERCE1 WWM REVIEW Needs Review
06/09/2011 CPIERCE1 ZONING REVIEW Needs Review
06/09/2011 CPIERCE1 ENGINEERING REVIEW Needs Review