Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01781
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/07/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/07/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/07/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/07/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1: WATER DISPENSER ON REFRIGERATOR MUST MEET ICC/ANSI A117.1-2003 REQUIREMENTS FOR A HIGH/LOW FOUNTAIN OR SINGLE POINT OF USE DISPENSER. PROVIDE VERBIAGE FOR THIS. 2. SHEET A1; NOTE AT RESTROOM: A NOTE INDICATES A TILE WAINSCOT TO 42" ABOVE FINISH FLOOR. IBC SECTION 1210.2 REQUIRES 48". REVISE. |
06/07/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
06/07/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/07/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/07/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
06/09/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/09/2011 | MARTIN BROWN | FIRE | REVIEW | Approved |