07/18/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01764
4757 E Camp Lowell Dr
11.270 KW Photovoltaic System

1. Sheet E-3 showing the existing Meter, feeds the new tap box,the the tap box then feeds the existing Bldg AC disconnect, the tap box also feeds the new PV System Disconnect.
Sheet E-4 shows the Existing Meter feeding the tap box, the tap box then goes back to the Existing Meter then on the the Bldg AC disconnect. The tap box also then feeds onto the New PV System disconnect. Need to make these the same.If the actual installation will be as on E-4, both plans to be the same.
2. Sheet E-3 Subarray 2, 3 strings totaling 37.64 amps, going through a 3 pole 20 A disconnect, is each leg protected at 20 amps ?
3. Indicate amperage fuse at New PV System Disconnect.
4. Indicate the size in amperage and voltage of the existing
service being Tapped into.


Ray T Majuta
Elect Pln Ck
PDSD City of Tucson
7/20/11