Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01764
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE STRUCTURAL CALCULATIONS, SIGNED, SEALED, AND DATED BY A LICENSED ENGINEER, INDICATING THE ADEQUACY OF THE EXISTING ROOF STRUCTURE TO SUPPORT THE NEW PHOTOVOLTAIC LOADS.
2. GENERAL: PROVIDE STRUCTURAL CALCULATIONS, SIGNED, SEALED AND DATED BY A LICENSED ENGINEER, INDICATING THE AMOUNT OF LATERAL LOAD ON THE NEW PHOTOVOLTAIC PANELS, AND THE DESIGN OF THE NEW CONNECTORS OF THE PHOTOVOLTAIC PANELS TO THE EXISTING ROOF STRUCTURE. PROVIDE DETAILS AS REQUIRED.
06/29/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM01764
4757 E Camp Lowell
11,270 watt PV sys

The electrical plans have been denied for the following:

1. The min font size for all lettering and numbers is 1/8''.
2. The background line on sheets E1 and E-3 are too light.
3. The specification sheets are too light.

Items 1 and 2 above are required to be dark enough to record, be scanned, and put into files.

4. The values for the panel used on sheet E-1 stated for Centrosolar C-230, do not match what is shown on the spec sheet ? The spec sheet states CM6 230SW.
5. Provide a drawing of how the building service, the tap box, the existing building AC disconnect, new PV system disconnect, PV meter, the combiner panel,the inverters,PV dc disconnect will located according to one another, once installed. The drawings state on the south wall of building.
6. How have the roof mounted conductors been factored according to 2005 NEC Table 315.16 Ambient Temperature
values.
7. Show how the 6 # 10's (conductors) in one 3/4" conduit
have been derated per 2005 NEC 310.15.B.2.a .



Ray T Majuta
Elect Pln Ck, PDSD,
City of Tucson,
6/30/11