Review Details: REVISION - - 1ST
Permit Number - T11CM01744
Review Name: REVISION - - 1ST
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the design of the drain standpipes described in keynotes 30 and 31. Standpipe receptors shall have their traps located 6" to 18" above the floor and the standpipe shall terminate between 18" and 30" above its trap (Section 804.1, UPC 2006). If the trap is to be located below the floor, the drain shall comply with Sections 411.1 and 804.1, UPC 2006. 2. Provide structural calculations and construction details fo the design of the backwash fines separation tank, including the traffic rating for the tank cover. reference: Sections 1009.0 and 1016.0, UPC 2006. |