Permit Number: T11CM01744
Parcel: 140280170

Address:
2209 E GINTER RD

Review Status: Active

Review Details: REVISION - - 1ST

Permit Number - T11CM01744
Review Name: REVISION - - 1ST
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the design of the drain standpipes described in keynotes 30 and 31. Standpipe receptors shall have their traps located 6" to 18" above the floor and the standpipe shall terminate between 18" and 30" above its trap (Section 804.1, UPC 2006). If the trap is to be located below the floor, the drain shall comply with Sections 411.1 and 804.1, UPC 2006.
2. Provide structural calculations and construction details fo the design of the backwash fines separation tank, including the traffic rating for the tank cover. reference: Sections 1009.0 and 1016.0, UPC 2006.