Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01741
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T1.0; PLUMBING FIXTURE CALCULATION: REVISE THE NUMBER OF OCCUPANTS USING 30 SF/PERSON PER 2006 IBC TABLE 1004.1.1. 2. SHEET T1.0; ACCESSIBILITY UPGRADES: THE NEW SERVICE DESK WITH ACCESSIBLE COUNTER CAN NOT BE CONSIDERED FOR THE 20% FOR ACCESSIBILITY ISSUES. 3. SHEET C1.0; DEMOLITION PLAN: CORRECTLY DEPICT THE EXISTING RESTROOMS ON THE DRAWING. 4. SHEET A1.0; FLOOR PLAN KEYNOTES: REVISE NOTE 10 TO INDICATE SINGLE POINT-OF-USE WATER DISPENSER. 5. SHEET A1.0; FLOOR PLAN: PER LEERAY HANLY, THE SERVICE SINK (KEYNOTE 9) MAY BE REMOVED FROM THE PLAN. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/23/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/29/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/30/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |