Permit Number: T11CM01741
Parcel: 10611005A

Address:
1881 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01741
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2011 CARL SCHULTZ FIRE REVIEW Approved
06/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that adequate ventilation is being provided.
06/03/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PROVIDE INFORMTION FOR PROPER TERMINATION OF REMOVED ELECTRICAL DEVICES

PROVIDE DETAILS FOR NEW LIGHTING, INCLUDING CORRECT IECC COMPLIANCE INFORMATION
06/03/2011 ROBERT SHERRY WATER REVIEW Approved
06/03/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0: THIS PLAN HAS EXITING ISSUES. IF WE ARE CONSIDERING THE DOORS ON THE SOUTH WALL AS EXITS, EGRESS THROUGH A MERCANTILE STOCKROOM MUST MEET THE FOUR REQUIREMENTS OF THE IBC SECTION 1014.2 (2.1, 2.2, 2.3, AND 2.4). IF WE ARE JUST USING THE EXIT ON THE NORTH WALL, THE MAXIMUM TRAVEL DISTANCE FOR ONE EXIT PER IBC TABLE 1019.2 IS 75 FEET. THAT DISTANCE IS EXCEEDED ON THIS PLAN. CLARIFY AND REVISE THE PLAN.
2. PER THE IBC, TABLE 2902.1, A HIGH/LOW DRINKING FOUNTAIN (OR SINGLE POINT-OF-USE DISPENSER) IS REQUIRED, AND A MOP SINK IS REQUIRED. VERIFY.
3. PER THE IBC, SECTION 3409.7, INDICATE ON THE PLANS HOW A MAXIMUM OF 20% OF THE PROJECT BUDGET IS BEING SPENT ON ACCESSIBILITY ISSUES.
06/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy.
2. Show how the existing plumbing will be capped when the existing sink is removed.
06/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed 1. SHEET A1.0: THIS PLAN HAS EXITING ISSUES. IF WE ARE CONSIDERING THE DOORS ON THE SOUTH WALL AS EXITS, EGRESS THROUGH A MERCANTILE STOCKROOM MUST MEET THE FOUR REQUIREMENTS OF THE IBC SECTION 1014.2 (2.1, 2.2, 2.3, AND 2.4). IF WE ARE JUST USING THE EXIT ON THE NORTH WALL, THE MAXIMUM TRAVEL DISTANCE FOR ONE EXIT PER IBC TABLE 1019.2 IS 75 FEET. THAT DISTANCE IS EXCEEDED ON THIS PLAN. CLARIFY AND REVISE THE PLAN.
2. PER THE IBC, TABLE 2902.1, A HIGH/LOW DRINKING FOUNTAIN (OR SINGLE POINT-OF-USE DISPENSER) IS REQUIRED, AND A MOP SINK IS REQUIRED. VERIFY.
3. PER THE IBC, SECTION 3409.7, INDICATE ON THE PLANS HOW A MAXIMUM OF 20% OF THE PROJECT BUDGET IS BEING SPENT ON ACCESSIBILITY ISSUES.
06/03/2011 ERIC NEWCOMB ADA REVIEW Passed
06/21/2011 CPIERCE1 WWM REVIEW Needs Review
06/21/2011 CPIERCE1 ZONING REVIEW Needs Review
06/21/2011 CPIERCE1 ENGINEERING REVIEW Needs Review