Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM01723
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2011 GERRY KOZIOL WWM REVIEW Denied NEED COT REVIEW & APPROVAL OF GREYWATER SYSTEM
NEED 2 WAY VALVE ON GREYWATER SYSTEM TO CHANEL WATER TO SEWER OR LANDSCAPE
06/30/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 7-1-11
Activity: T11CM01723
Address: 514 E 1st St
Applicant: Gal Witmer

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Provide section view and details for proposed chimney, R801.2.
2. Specify lumber grade/species, or manufacturer and series for "I" joists, R802.1.

PLUMBING PLAN:
3. Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1.
4.
ELECTRICAL PLAN:
5. Show receptacle outlets at each kitchen counter space wider than 12" so that no point along the wall line is more than 24" from a receptacle outlet, E3801.4.1.
6. Island or peninsula counter tops with a long dimension of 24" and a short dimension of 12" or greater shall have at least one receptacle, E3801.4.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2011 CPIERCE1 OUT TO CUSTOMER Completed
07/18/2011 SUE REEVES REJECT SHELF Completed