Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM01716
Parcel: 117130410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01716
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

1. Fire alarm notification devices shall be installed in public areas per IFC Section 907.10.1.1.

2. All apartments shall be pre-wired for visible alarms per IFC 907.10.1.4.

3. Provide cut sheets for the rotating 20 minute door to comply with IFC Table 1017.1.
06/15/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP C1 NON RESPONSIVE TO ORIGINAL COMMENT---DELETE REFERENCES TO IRC FROM CODE ANALYSIS

PP A-1 NON RESPONSIVE OR INCOMPLETE

b) INCOMPLETE--ADDING CAULK AT TOP OF WALL DOES NOT ADDRESS WHAT HAPPENS THROUGH ROOF EXPANSION & CONTRACTION IF TOP TRACK IS SCREWED OFF TO DRYWALL (WHICH WOULD BE A STANDARD INSTALLATION)

e) NON RESPONSIVE-- THERE WAS NO COMMENT MADE ABOUT THE GUARD RAIL NOR THE EXISTING HANDRAILS IN THE STAIRS. PROVIDE DIMENSIONED DETAILS AND DETAIL REFERENCES FOR HANDRAILS (THE NEW ONES INSIDE THIS SUITE) FIREPLACES, FIRE-PITS, CABINETRY, ETC. CUT SHEETS ARE IN ADDITION TO REQUIRED INFORMATION ON PLAN SHEETS.

PP A-3 UNRESPONSIVE TO CORRECTION COMMENTS

a) INCOMPLETE INFORMATION PROVIDED
b) CORRECTION NOT MADE


ADDITIONAL COMMENTS DUE TO ON SITE INSPECTIONS OF WORK

1) PROVIDE COMPLETE DETAILS FOR ALL SOFFITS

2) PROVIDE INFORMATION VERIFYING 20 MIN RATING OF CUSTOM MADE ENTRY DOOR

3) REVISE ALL MECHANICAL PLANS TO MATCH AS-BUILT.