Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: 1. Fire alarm notification devices shall be installed in public areas per IFC Section 907.10.1.1. 2. All apartments shall be pre-wired for visible alarms per IFC 907.10.1.4. 3. Provide cut sheets for the rotating 20 minute door to comply with IFC Table 1017.1. |
06/15/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PP C1 NON RESPONSIVE TO ORIGINAL COMMENT---DELETE REFERENCES TO IRC FROM CODE ANALYSIS PP A-1 NON RESPONSIVE OR INCOMPLETE b) INCOMPLETE--ADDING CAULK AT TOP OF WALL DOES NOT ADDRESS WHAT HAPPENS THROUGH ROOF EXPANSION & CONTRACTION IF TOP TRACK IS SCREWED OFF TO DRYWALL (WHICH WOULD BE A STANDARD INSTALLATION) e) NON RESPONSIVE-- THERE WAS NO COMMENT MADE ABOUT THE GUARD RAIL NOR THE EXISTING HANDRAILS IN THE STAIRS. PROVIDE DIMENSIONED DETAILS AND DETAIL REFERENCES FOR HANDRAILS (THE NEW ONES INSIDE THIS SUITE) FIREPLACES, FIRE-PITS, CABINETRY, ETC. CUT SHEETS ARE IN ADDITION TO REQUIRED INFORMATION ON PLAN SHEETS. PP A-3 UNRESPONSIVE TO CORRECTION COMMENTS a) INCOMPLETE INFORMATION PROVIDED b) CORRECTION NOT MADE ADDITIONAL COMMENTS DUE TO ON SITE INSPECTIONS OF WORK 1) PROVIDE COMPLETE DETAILS FOR ALL SOFFITS 2) PROVIDE INFORMATION VERIFYING 20 MIN RATING OF CUSTOM MADE ENTRY DOOR 3) REVISE ALL MECHANICAL PLANS TO MATCH AS-BUILT. |