Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL SITE PLANS REFER TO A SIZE 7 PULL BOX. PLEASE SPECIFY ACTUAL DIMENSIONS OF BOX.

PP E2.2 HAS 2 CUT REFERENCES TO 9/E4.1; DO YOU MEAN 8/E4.1?

PP E2.1 & E2.2 KEYNOTE 3...PLAN VIEW DOES NOT INDICATE CKT, CONDUIT OR WIRE SIZE

PP E3.1 A SINGLE SET OF #500 KCMIL MV 105 CONDUCTORS IS INSUFFICIENT FOR 600A. (NEC TABLE 310.77)

PLEASE ADD CONDUCTOR TYPE TO FEEDER SCHEDULE ON PP E3.1 AS AN AID TO THE FIELD INSPECTOR

ERRATA: PANEL SCHEDULE PP E4.2 HAS PANEL LABELED L-LP, SHOULD BE L-PL FOR CONSISTENCY WITH PLANS.

PLEASE INCLUDE OUTDOOR LIGHTING CODE COMPLIANCE INFORMATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2011 CPIERCE1 OUT TO CUSTOMER Completed
07/12/2011 SUE REEVES REJECT SHELF Completed