Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL SITE PLANS REFER TO A SIZE 7 PULL BOX. PLEASE SPECIFY ACTUAL DIMENSIONS OF BOX. PP E2.2 HAS 2 CUT REFERENCES TO 9/E4.1; DO YOU MEAN 8/E4.1? PP E2.1 & E2.2 KEYNOTE 3...PLAN VIEW DOES NOT INDICATE CKT, CONDUIT OR WIRE SIZE PP E3.1 A SINGLE SET OF #500 KCMIL MV 105 CONDUCTORS IS INSUFFICIENT FOR 600A. (NEC TABLE 310.77) PLEASE ADD CONDUCTOR TYPE TO FEEDER SCHEDULE ON PP E3.1 AS AN AID TO THE FIELD INSPECTOR ERRATA: PANEL SCHEDULE PP E4.2 HAS PANEL LABELED L-LP, SHOULD BE L-PL FOR CONSISTENCY WITH PLANS. PLEASE INCLUDE OUTDOOR LIGHTING CODE COMPLIANCE INFORMATION. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/12/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
07/12/2011 | SUE REEVES | REJECT SHELF | Completed |