Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01714
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 06/02/2011 | LHANLY1 | WATER | REVIEW | Passed | |
| 06/02/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/02/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/02/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/02/2011 | LHANLY1 | WWM | REVIEW | Passed | |
| 06/02/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/02/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/02/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 06/02/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/02/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PER THE 2006 IBC, SECTION 1607.13, INTERIOR WALLS MUST BE DESIGNED TO RESIST A HORIZONTAL LOAD OF 5 PSF. PROVIDE A DETAIL AT THE TOP OF THE WALL AND AT THE STRUCTURE ABOVE, INDICATING DIAGONAL BRACING. INDICATE SIZE AND SPACING OF THE BRACING, HOW IT IS CONNECTED TO THE STRUCTURE ABOVE, AND HOW IT IS CONNECTED TO THE TOP OF THE WALL. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |