Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01705
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. Provide structural calculations for the new cooling tower base support (detail 113/M2.0) and clarify the installation of the support. Provide dimensions for the proposed bases, the number of bases to be used, and the bearing surface for the foot pads. Reference: Sections 106.3.1, IMC 2006. |
08/01/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |