Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01705
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations for the new cooling tower base support (detail 113/M2.0) and clarify the installation of the support. Provide dimensions for the proposed bases, the number of bases to be used, and the bearing surface for the foot pads. Show also that the discharge plume location conforms to the requirements of Section 908.3, IMC 2006. Reference: Sections 106.3.1, 908.1, and 908.4 IMC 2006. |
07/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Detail 205/P0.0, "Mech Yard Sump Pump Detail", shows a floor drain located in a concrete basin but no sump pump (I assume that you don't intend to install a sump pump). Specify the floor drain and indicate how it is to be installed in the basin to form a watertight joint, Reference: Section 411.1, UPC 2006. [Original comment: Coordinate the plumbing schedule entry and the fixture specification for the floor sink, P-1. Clarify why the 3" waste pipe for P-1 has a 4" vent. Reference: Section 103.2.3, UPC 2006.] |
07/18/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/19/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/01/2011 | GERARDO BONILLA | APPROVAL SHELF | Completed |
08/01/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
08/01/2011 | GERARDO BONILLA | REJECT SHELF | Completed |