Permit Number: T11CM01705
Parcel: 13220003A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01705
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations for the new cooling tower base support (detail 113/M2.0) and clarify the installation of the support. Provide dimensions for the proposed bases, the number of bases to be used, and the bearing surface for the foot pads. Show also that the discharge plume location conforms to the requirements of Section 908.3, IMC 2006. Reference: Sections 106.3.1, 908.1, and 908.4 IMC 2006.
07/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Detail 205/P0.0, "Mech Yard Sump Pump Detail", shows a floor drain located in a concrete basin but no sump pump (I assume that you don't intend to install a sump pump). Specify the floor drain and indicate how it is to be installed in the basin to form a watertight joint, Reference: Section 411.1, UPC 2006. [Original comment: Coordinate the plumbing schedule entry and the fixture specification for the floor sink, P-1. Clarify why the 3" waste pipe for P-1 has a 4" vent. Reference: Section 103.2.3, UPC 2006.]
07/18/2011 STEVE SHIELDS ZONING REVIEW Approved
07/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2011 GERARDO BONILLA APPROVAL SHELF Completed
08/01/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
08/01/2011 GERARDO BONILLA REJECT SHELF Completed