Permit Number: T11CM01705
Parcel: 13220003A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01705
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing schedule entry and the fixture specification for the floor sink, P-1. Clarify why the 3" waste pipe for P-1 has a 4" vent. Reference: Section 103.2.3, UPC 2006.
2. Indicate the materials to be used in the proposed plumbing systems for this activity. Reference: Sections 103.2.3, 301.1, 604.0, 701.0, 903.0, and 1209.5, UPC 2006. (Note: ABS building sewers over 60 feet long with slopes less than ΒΌ" per foot require special inspection for slope.)
3. Specify the freeze protection for the water supply piping to the hose bibbs and to the cooling towers. Reference: Section 313.6, UPC 2006.
4. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference: Section 719.1, UPC 2006.
06/14/2011 ROBERT SHERRY WATER REVIEW Approved
06/14/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
2. Specify the insulation to be used for the chilled water and heating water piping on this project. Reference: Section 503.2.8, IECC 2006.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
4. Provide a design for the condensate dry wells. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
5. Provide calculations to show that the specified machinery room ventilation system complies with Section 1105, IMC 2006.
06/20/2011 GERRY KOZIOL WWM REVIEW Approved
06/22/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: SouthWest Gas - Mechanical Building
T11CM01705
Building Plan (1st Review)

TRANSMITTAL DATE: June 22, 2011


1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until a revised development plan has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t11cm01705.doc
06/28/2011 PAUL MACHADO ENGINEERING REVIEW Approved
06/29/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2011 DELMA ROBEY OUT TO CUSTOMER Completed