Permit Number: T11CM01680
Parcel: 10408077E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01680
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2011 TERRY STEVENS ZONING REVIEW Approved
06/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved .
06/01/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2011 ROBERT SHERRY WATER REVIEW Approved
06/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2011 LOREN MAKUS ENGINEERING REVIEW Approved
06/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A 1-1/2" vent can accomodate up to 8 fixture units and can have a maximum horizontal length of 20 feet. Indicate the total connected load for the new 1-1/2" vent and the existing 1-1/2" vent. Limit the horizontal length of the 1-1/2" vent to less than 20 feet or increase the size of the vent to 2" over its total length.
2. Provide a reduced pressure zone backflow preventer for the carbonator.
3. Specify the piping materials to be used or include a reference copy of the drawing that does specify the materials.
4. Provide the total demand that the water meter is handling.
06/01/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/01/2011 ERIC NEWCOMB ADA REVIEW Passed
06/02/2011 DAVE MANN FIRE REVIEW Approved
06/14/2011 CPIERCE1 WWM REVIEW Needs Review