| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | . |
| 06/01/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/01/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/01/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/01/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/01/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A 1-1/2" vent can accomodate up to 8 fixture units and can have a maximum horizontal length of 20 feet. Indicate the total connected load for the new 1-1/2" vent and the existing 1-1/2" vent. Limit the horizontal length of the 1-1/2" vent to less than 20 feet or increase the size of the vent to 2" over its total length. 2. Provide a reduced pressure zone backflow preventer for the carbonator. 3. Specify the piping materials to be used or include a reference copy of the drawing that does specify the materials. 4. Provide the total demand that the water meter is handling. |
| 06/01/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/01/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 06/02/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/14/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |