Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM01678
Parcel: 12212039C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01678
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2011 TERRY STEVENS ZONING REVIEW Approved
06/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/01/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PROVIDE AIC RATINGS FOR PANELS AND AVAILABLE GROUND FAULT CALCULATIONS.
06/01/2011 ROBERT SHERRY WATER REVIEW Approved
06/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2011 LOREN MAKUS ENGINEERING REVIEW Approved
06/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing plan and the riser diagram.
2. Provide a reduced pressure zone backflow preventor for the carbonator (health hazard , back-siphonage, and back-pressure).
3. Correct the size of the building drain downstream of the water closet.
4. Specify the piping materials to be used or include a reference copy of the drawing that does specify the materials.
5. Provide the total demand that the water meter is handling.
6. Provide a vent for the floor sink trap.
06/01/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/01/2011 ERIC NEWCOMB ADA REVIEW Passed
06/02/2011 DAVE MANN FIRE REVIEW Approved
06/14/2011 CPIERCE1 WWM REVIEW Needs Review