Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01678
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/01/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROVIDE AIC RATINGS FOR PANELS AND AVAILABLE GROUND FAULT CALCULATIONS. |
06/01/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/01/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/01/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
06/01/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing plan and the riser diagram. 2. Provide a reduced pressure zone backflow preventor for the carbonator (health hazard , back-siphonage, and back-pressure). 3. Correct the size of the building drain downstream of the water closet. 4. Specify the piping materials to be used or include a reference copy of the drawing that does specify the materials. 5. Provide the total demand that the water meter is handling. 6. Provide a vent for the floor sink trap. |
06/01/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/01/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
06/02/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
06/14/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |