Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

If the new occupant load uner roof exceeds 100 automatic sprinklers will be required. See IFC Chapter 9.
06/06/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Teresa's Mosaic Cafe
T11CM01665
Site Plan (1st Review)

TRANSMITTAL DATE: June 7, 2011

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the areas of expansion and any changes to the site.

2. As this is not an approved site plan and no revisions have been made remove all revision clouds from the plan.

3. D.S. 2-02.2.1.A.2 Provide a property description, legal description, on the site plan.

4. D.S. 2-02.2.1.A.19 Provide the right-of-way dimensions for N. Silver Mosaic Dr.

5. D.S. 2-02.2.1.A.20 Show all easements of record graphically on the plan along with the recordation information, docket and page/sequence number.

6. D.S. 2-02.2.1.A.31 Provide the existing use on the plan as; "FOOD SERVICE "28", SUBJECT TO: SEC. 3.5.4.6.A AND .C."

7. D.S. 2-02.2.2.A.1 Provide the gross lot area on the plan.

8. D.S. 2-02.2.2.A.2 The provided "Existing building" square footage (sq. ft.) appears to be incorrect. Based on the provided last approved site plan the existing building sq. ft. was listed as 3,760 sq. ft., clarify the difference.

9. D.S. 2-02.2.2.A.2 The sq. ft. listed under "SQUARE FOOTAGE" for the "Addition" shows 465 sq. ft. The note on the plan pointing to the addition shows 443 sq. ft, clarify the difference.

10. D.S. 2-02.2.2.A.3 Provide a Floor Area Ration (FAR) calculation on the plan that includes the allowed and proposed FAR.

11. D.S. 2-02.2.2.A.4 Until comments 8 & 9 are addressed the vehicle parking calculation cannot be verified.

12. D.S. 2-02.2.2.A.5 Provide loading space calculation on the plan that includes the required and provided.

13. D.S. 2-02.2.2.A.6 Provide a building expansion calculation on the plan.

14. As a general note provide the Scenic Corridor Zone (SCZ) number, T11SA00046, date of approval and any associated conditions of approval on the plan.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\2011\t11cm01665

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan.
06/08/2011 RONALD BROWN H/C SITE REVIEW Approved
06/20/2011 ANDREW CONNOR LANDSCAPE REVIEW Passed
06/20/2011 ANDREW CONNOR NPPO REVIEW Passed
06/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the fire hydrants
c. the location of the building connection to the public sewer
d. the location, invert, and rim elevation of the upstream and downstream manholes
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2011 DELMA ROBEY OUT TO CUSTOMER Completed