Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation design to provide local capture of the contaminants and odors for the nail polish application areas. The two manicure stations each require local exhaust. Reference: Section 403.3 and Table 403.3,footnote (i), IMC 2006. 2. Specify how the local exhaust points for the pediicure chairs are located (i.e. how high above the floor?). |
06/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water calculations to account for the required minimum pressure of 30 PSI (Pedicure) and revise the water pipe sizes accordingly. 2. Limit the water velocity to 8 FPS for cold water and 5 FPS for hot water. Reference: Section 610.12, UPC 2006. 3. Include the fixture units for both the pedicure chairs (2 supply, 2 waste) and for the clothes washer (4 supply and 3 waste). |