Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM01642
Parcel: 105110660

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01642
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation design to provide local capture of the contaminants and odors for the nail polish application areas. The two manicure stations each require local exhaust. Reference: Section 403.3 and Table 403.3,footnote (i), IMC 2006.
2. Specify how the local exhaust points for the pediicure chairs are located (i.e. how high above the floor?).
06/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water calculations to account for the required minimum pressure of 30 PSI (Pedicure) and revise the water pipe sizes accordingly.
2. Limit the water velocity to 8 FPS for cold water and 5 FPS for hot water. Reference: Section 610.12, UPC 2006.
3. Include the fixture units for both the pedicure chairs (2 supply, 2 waste) and for the clothes washer (4 supply and 3 waste).