Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM01642
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation design to provide local capture of the contaminants and odors for the nail polish application areas. Reference: Section 403.3 and Table 403.3,footnote (i), IMC 2006. |
| 05/31/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/31/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/31/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please provide an accecessible water dispenser as per ANSI SECTION 602.4 or a Point of Use Water Dispenser. |
| 05/31/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 05/31/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/31/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/01/2011 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 06/01/2011 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/01/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/01/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |