Permit Number: T11CM01641
Parcel: 117062100

Address:
128 S HERBERT AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM01641
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2011 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation.
need PC Adressing for units
08/15/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied LISTED REPAIRS TO APT 3 DO NOT ADDRESS REQUIRED FIRE DAMAGE REPAIRS INDICATED IN EMERGENCY CALL FROM 1-10-2010 (T10DV00127)

PROVIDE DETAILS FOR NEW LINTEL IN MASONRY WALL FOR APT 3.

PLEASE SHOW KITCHEN LAYOUT OF APT 3.

PROVIDE DETAILS FOR NEW METAL STUD WALL INFILL & WINDOW INSTALLATIONS (KEYNOTES 4 & 5 PP A.3)
08/15/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied PROVIDE PLUMBING DETAILS FOR NEW KITCHEN AREA OF APT. 3.
08/15/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied ARCHITECTURAL FLOOR PLANS DO NOT MATCH ELECTRICAL FLOOR PLANS
a) PLEASE MAINTAIN CONSITENT 'NORTH' ORIENTATION
b) SHOW KITCHEN OF APT 3

NEW CIRCUITS FOR APT 3 KITCHEN TO BE FED FROM PANEL 'C', NOT FROM HOUSE PANEL.
08/15/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied PROVIDE HEATING AND COOLING INFORMATION FOR ALL APARTMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2011 DELMA ROBEY OUT TO CUSTOMER Completed
11/04/2011 SUE REEVES REJECT SHELF Completed