Permit Number: T11CM01630
Parcel: 14032003A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01630
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2011 STEVE SHIELDS ZONING REVIEW Passed
07/25/2011 DAVE MANN FIRE REVIEW Approved
07/29/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2011 GERRY KOZIOL WWM REVIEW Denied NEED DEQ REVIEW & APPROVAL OF RELOCATION OF EXSISTING ON-SITE PRIVATE SEWER WITH MANHOLES- DAVE AMASH- 243-7400
NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE
NEED CAPACITY REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- PCRWRD/ 3RD FLOOR- CHAD- 740-6547
NEED WW/IWC REVIEW OF NEUTRALIZATION BASIN FOR LAB SINKS- TOM TOMCHAK- 443-6200
08/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; the combination drain and vent system on the second floor connects to a stack, not to a building drain. Determine the maximum number of drainage fixture units for each branch using the first column of Table 912.3, IPC 2006. According to Table 912.3, a 3" pipe can accommodate 12 drainage fixture units, a 4" pipe can accommodate 20 drainage fixture units, and a 5" pipe is required for up to 160 drainage fixture units. [Original comment: Revise the pipe sizes for the combination drain and vent systems shown in the second floor lab (west, detail 4/P2.0); horizontal branches shall be sized per Table 912.3, IPC 2006.]
08/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
08/15/2011 SUE REEVES REJECT SHELF Completed