Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM01630
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2011 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
07/25/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
07/29/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/03/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED DEQ REVIEW & APPROVAL OF RELOCATION OF EXSISTING ON-SITE PRIVATE SEWER WITH MANHOLES- DAVE AMASH- 243-7400 NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE NEED CAPACITY REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- PCRWRD/ 3RD FLOOR- CHAD- 740-6547 NEED WW/IWC REVIEW OF NEUTRALIZATION BASIN FOR LAB SINKS- TOM TOMCHAK- 443-6200 |
08/11/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the combination drain and vent system on the second floor connects to a stack, not to a building drain. Determine the maximum number of drainage fixture units for each branch using the first column of Table 912.3, IPC 2006. According to Table 912.3, a 3" pipe can accommodate 12 drainage fixture units, a 4" pipe can accommodate 20 drainage fixture units, and a 5" pipe is required for up to 160 drainage fixture units. [Original comment: Revise the pipe sizes for the combination drain and vent systems shown in the second floor lab (west, detail 4/P2.0); horizontal branches shall be sized per Table 912.3, IPC 2006.] |
08/11/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/15/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
08/15/2011 | SUE REEVES | REJECT SHELF | Completed |