Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM01629
Parcel: 14022002A

Address:
1725 E BILBY RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM01629
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2011 DAVE MANN FIRE REVIEW Approved
07/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/27/2011 GERRY KOZIOL WWM REVIEW Denied 1. HIGH SCHOOL - " NEW BUILDING SPACE" NO DEMO - WITHIN NEW ASSUMED PROPERTY LINES PER SITE ANALYSIS G1.3

2. CONNECTING TO EXISTING 8" PUBLIC SEWER WITH A 4" ON SITE PRIVATE SEWER

3. NEED COPY OF RICK ENGINEERING DRAWING "C3" FOR 4" ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE - (IF OVER 3000 GL / DAY NEED DEQ REVIEW & APPROVAL TO CONSTRUCT)

4. NEED 3RD FLOOR PCRQRD REVIEW & APPROVAL OF CAPACITY - CHAD AMATEAU 740-6547

5. NEED IWC/ REVIEW & APPROVAL OF ACID NEUTRALIZATION TANK FRO SCIENCE ROOM LABS - TOM TOMCHAK - 443-6200 - 5025 W. INA RD
08/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide cleanouts for the 3" acid waste system, located not more than 100 feet apart and sized for the pipe they serve. Reference: Sections 708.3 and 708.7, IPC 2006.
2. Correct the total gas load on the gas meter serving the west building. The drawing appears to show a total connected load of 1148 CFH but the note by the gas meter indicates a load of 1510 CFH; where is the additional 362 CFH connected?

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2011 CPIERCE1 OUT TO CUSTOMER Completed
08/11/2011 SUE REEVES REJECT SHELF Completed